| Line 1: | Line 1: | ||
| - | ====== TechTip: ====== | + | ====== TechTip: |
| - | ===== Basic Analog Input Signal Connections (Part 2) ===== | + | **Objective**\\ |
| - | + | ||
| - | *Objective**\\ | + | |
| To provide DAQ product users with recommended single-ended/ | To provide DAQ product users with recommended single-ended/ | ||
| Line 13: | Line 11: | ||
| **Recommended analog input configuration (based on a DAQ device with ±10 V common mode range)**\\ | **Recommended analog input configuration (based on a DAQ device with ±10 V common mode range)**\\ | ||
| - | ^ Ground Relationship between\\ Sensor and DAQ ^ DAQ Input Configuration | + | ^ Ground Relationship between\\ Sensor and DAQ ^ DAQ Input Configuration |
| | Common ground | | Common ground | ||
| | Common ground | | Common ground | ||
| Line 31: | Line 29: | ||
| MCC recommends using a single-ended configuration for the common ground scenario. However, if only some input channels/ | MCC recommends using a single-ended configuration for the common ground scenario. However, if only some input channels/ | ||
| - | {{https:// | + | {{https:// |
| **Figure 1.** Signal source and AI DAQ device sharing common ground connected to single-ended input\\ | **Figure 1.** Signal source and AI DAQ device sharing common ground connected to single-ended input\\ | ||
| - | {{https:// | + | {{https:// |
| **Common Ground / Differential Inputs**\\ | **Common Ground / Differential Inputs**\\ | ||
| Using a differential configuration is acceptable for common ground connections, | Using a differential configuration is acceptable for common ground connections, | ||
| - | {{https:// | + | {{https:// |
| **Figure 2.** Signal source and AI DAQ device sharing common ground connected to differential input\\ | **Figure 2.** Signal source and AI DAQ device sharing common ground connected to differential input\\ | ||
| Line 75: | Line 73: | ||
| For the best performance with isolated signal sources, MCC recommends using a differential input configuration. Figure 7 shows the recommended connections for this configuration.\\ | For the best performance with isolated signal sources, MCC recommends using a differential input configuration. Figure 7 shows the recommended connections for this configuration.\\ | ||
| - | {{https:// | + | {{https:// |
| **Figure 7.** Isolated signal source connected to differential input\\ | **Figure 7.** Isolated signal source connected to differential input\\ | ||
| + | **More Information**\\ | ||
| + | Please reach out to our support team on the Digilent Forum if you have any questions: [[https:// | ||
| + | | ||
| + | Additional TechTips are available here in Digilent Reference: [[start]] | ||